ASTM F1974-00a
Historical Standard: ASTM F1974-00a Standard Specification for Metal Insert Fittings for Polyethylene/Aluminum/Polyethylene and Crosslinked Polyethylene/Aluminum/Crosslinked Polyethylene Composite Pressure Pipe
SUPERSEDED (see Active link, below)
ASTM F1974
1. Scope
1.1 This specification covers metal insert fittings with split ring and compression nut (compression joint) and metal insert fittings with copper crimp rings (crimp joint) for four sizes of composite pressure pipe. These fittings are intended for use in 125 psi (690 kPa) cold- and hot-water distribution systems operating at temperatures up to and including 180 o F (82 o C). (When used in polyethylene/aluminum/polyethylene systems the maximum operating temperature is limited by the pipe to 140 F (60 o C) and where applicable 180 o F (82 o C)). Included are the requirements for materials, workmanship, burst pressure, sustained pressure, excessive temperature and pressure, temperature cycling tests, and markings to be used on the fittings and rings. The fittings covered by this specification are intended for use in potable water distribution systems for residential and commercial applications, water service, underground irrigation systems, and radient panel heating systems, baseboard, snow- and ice-melt systems, and gases that are compatible with the composite pipe and fittings.
1.2 The values stated in inch-pound units are to be regarded as the standard. The SI values stated in parentheses are provided for information purposes.
Note 1The tables show the 'nominal size' in millimetres with the inch size in parentheses. This exception is made to harmonize the 'nominal size' with the two pipe standards, F1281 and F1281.
1.3 The following precautionary caveat pertains only to the test method portion, Section 9, of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
2. Referenced Documents (purchase separately) The documents listed below are referenced within the subject standard but are not provided as part of the standard.
ASTM Standards
B16/B16M Specification for Free-Cutting Brass Rod, Bar and Shapes for Use in Screw Machines
B36/B36M Specification for Brass Plate, Sheet, Strip, And Rolled Bar
B62 Specification for Composition Bronze or Ounce Metal Castings
B75 Specification for Seamless Copper Tube
B134/B134M Specification for Brass Wire
B140/B140M Specification for Copper-Zinc-Lead (Red Brass or Hardware Bronze) Rod, Bar, and Shapes
B159/B159M Specification for Phosphor Bronze Wire
B283 Specification for Copper and Copper-Alloy Die Forgings (Hot-Pressed)
B371/B371M Specification for Copper-Zinc-Silicon Alloy Rod
B584 Specification for Copper Alloy Sand Castings for General Applications
D618 Practice for Conditioning Plastics for Testing
D1598 Test Method for Time-to-Failure of Plastic Pipe Under Constant Internal Pressure
D1599 Test Method for Resistance to Short-Time Hydraulic Pressure of Plastic Pipe, Tubing, and Fittings
D1600 Terminology for Abbreviated Terms Relating to Plastics
D2122 Test Method for Determining Dimensions of Thermoplastic Pipe and Fittings
D2240 Test Method for Rubber Property--Durometer Hardness
E18 Test Methods for Rockwell Hardness of Metallic Materials
F412 Terminology Relating to Plastic Piping Systems
F1281 Specification for Crosslinked Polyethylene/Aluminum/Crosslinked Polyethylene (PEX-AL-PEX) Pressure Pipe
F1282 Specification for Polyethylene/Aluminum/Polyethylene (PE-AL-PE) Composite Pressure Pipe
ANSI Standards
B16.22 Wrought Copper and Copper Alloy Solder Joint Pressure FittingsManufacturers Standardization Society Standard
SP-104 Wrought Copper LW Solder Joint Pressure Fittings Available from NSF International, P.O. Box 130140, 789 N. Dixboro Rd., Ann Arbor, MI 48113-0140, http://www.nsf.org.National Sanitation Foundation Standards
StandardNo.61 for Drinking Water System Components - Health EffectsKeywords
cold and hot water distribution; copper crimp rings; crosslinked polyethylene; metal insert fittings; polyethylene; PE/AL/PE; PEX/AL/PEX; PAP; Composites--piping applications (specifications); Copper crimp rings--specifications; Crosslinked polyethylene (PEX) pipe/tube--specifications; Hot water supply/distribution systems--specifications; Metal insert fittings--specifications; PAP; Cold water supply/distribution systems--specifications; PE/AL/PE pipe; PEX/AL/PEX pipe/tube; Polyethylene (PE) pipe--specifications ;
ICS Code
ICS Number Code 23.040.40 (Metal fittings)
DOI: 10.1520/F1974-00A
ASTM International is a member of CrossRef.