City of Santa Cruz Ordinance 2022-014: Amendments to 2022 California Codes, 2022
- [A] 109.6 – Overcrowding. Overcrowding or admittance of any person beyond the approved capacity of a building or a portion thereof shall not be allowed. The fire code official, upon finding any overcrowding conditions or obstructions in aisles, passag...
- “19.05.070 SECTION [A] 112.4 IS ADDED– VIOLATION PENALTIES.
- “19.05.080 SECTION [A] 112.4.1 AMENDED AND 112.4.2 ADDED—ABATEMENT OF VIOLATION; FAILURE TO COMPLY.
- STATE RESPONSIBILITY AREA (SRA) shall mean lands that are classified by the Board of Forestry pursuant to Public Resources Code Section 4125 to 4127; and the California Code of Regulations, Title14, Division 1.5, Chapter 7, Article 1, Sections 1220-12...
- “19.05.100 SECTION 304.1.2 IS AMENDED – VEGETATION.
- “19.05.200 SECTION 507.1 IS AMENDED – REQUIRED WATER SUPPLY.
- “19.05.220 CFC SECTIONS 903.1 THROUGH 903.2.10.2 ARE DELETED AND REPLACED – AUTOMATIC SPRINKLER SYSTEMS.
- Section 903.3.1.1.2 of Chapter 9 of the Fire Code of the city of Santa Cruz is deleted.”
- “19.05.240 SECTION 1103.5.5 IS ADDED – PYROXYLIN PLASTICS.
- “19.05.260 SECTION 3905.1.1 IS AMENDED – SAFETY SYSTEMS
- Section 3905.1.1 of Chapter 39 of the Fire Code of the city of Santa Cruz is amended to read as follows:
- 3905.1.1 – Operation. Activation of the gas detection system shall result in all of the following:
- 1. Initiation of distinct audible and visual alarm signals in extraction room.
- 2. Deactivation of all heating systems located in the extraction room.
- 3. Activation of the mechanical ventilation system, where the system is interlocked with gas detection.
- 4. De-energize all light switches and electrical outlets.
- 5. For detection levels at or exceeding 25% of the LEL/LFL shall result in the activation of the building’s fire alarm system.”
- “19.05.270 SECTION 4901.3 IS ADDED – REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AREAS.
- Section 4901.3 of Chapter 49 of the Fire Code of the city of Santa Cruz is added to read as follows:
- 4901.3 General. Areas identified within the Wildland-Urban Interface, as determined by the Fire Code Official, shall be held to all requirements as defined in Sections 4902.1 through 4910.4.
- 1. As determined by the Fire Code Official, construction requirements as identified in California Building Code, Chapter 7A, California Residential Code, Section R337 and California Referenced Standards Code, Chapter 12-7A shall apply to:
- a) All new construction
- b) All new materials used for additions and remodels.”
- “19.05.310 CHAPTER 90 IS ADDED – SUPPRESSION AND CONTROL OF WILDFIRE RISK AREAS. [Go to Page]